Tensile Strength of Flexible Conduit: What 500 N Means, and Why the Break Happens at the Fitting

We clamped a length of PA-6 Heavy Weight FR conduit between two fittings and pulled until something gave. It let go at 500 N. Here is what that number means for a real installation, and why the break happened where it did.

Synflex Technical Insights · 8 min read

A flexible conduit spends most of its life being pushed, bent and squeezed. It is not supposed to be pulled. Yet installations pull on conduit all the time: a fitter hauling cable through a long run, a machine guard that moves a little further than the drawing said, an unsupported drop that hangs from its top fitting, someone catching a foot on a run along the floor.

That is what a tensile test measures. We ran one on PA-6 Heavy Weight FR conduit in the Synflex test lab in Faridabad. The assembly separated at 500 N, about the weight of a 51 kg mass. This article explains what that number means, how standards classify it, and why the failure happened exactly where it did.

Video 1. Tensile test on PA-6 Heavy Weight FR conduit with a fitting at each end. The loading phase runs at 2× speed and the fracture is shown in slow motion. The conduit tears out of the upper fitting at 500 N.

What the test actually does

A conduit tensile test is carried out on a system, not on a loose length of tube. A sample of conduit is fitted with a connector at each end, exactly as it would be installed. The connectors are clamped in the jaws of a tensile tester: one fixed, one driven by a screw. The machine pulls the two ends apart at a steady rate while a load cell reads the force.

Watch the ruler beside the sample in the video. Before anything breaks, the conduit gets visibly longer. A corrugated tube is a spring: its ribs open out under tension long before the plastic itself is stretched hard. Only when the corrugations near a fitting have opened as far as they can does the load climb to the point of failure.

There are two ways to use the machine:

  • Class test. Pull to a set load from the standard, hold it, and check that nothing separates. This is how a product earns a class.
  • Test to failure. Keep pulling until something lets go, and record the peak force. This is what the video shows. It tells you where the real margin is.

How IEC 61386 classifies tensile strength

IEC 61386, the international standard for conduit systems for cable management, sorts conduit systems into classes for each mechanical property. For tensile strength the classes are:

ClassDescriptionTensile loadEquivalent mass
1Very light100 N≈ 10 kg
2Light250 N≈ 25 kg
3Medium500 N≈ 51 kg
4Heavy1,000 N≈ 102 kg
5Very heavy2,500 N≈ 255 kg

PA-6 Heavy Weight FR conduit is listed at 500 N, Class 3. Our test-to-failure result lands on that figure. For a flexible, lightweight corrugated conduit, Class 3 is a sound place to be. Heavier classes are usually the territory of rigid conduit or metal-reinforced flexible systems.

Why it broke at the fitting

Look at the slow-motion section of the video. The conduit does not snap in the middle of its length. It tears and pulls out where it enters the upper fitting. That is the expected failure mode for corrugated conduit, and it says something useful about how the system works.

PA-6 conduit tearing out of the upper fitting at the moment of tensile failure
Figure 1. The moment of failure: the corrugations just below the upper fitting have opened out and the conduit wall has torn at the joint.

A snap-in conduit fitting does not glue or weld onto the conduit. It holds it mechanically, with internal teeth or a claw that engage the valleys between the corrugation ribs. Under tension, the load path runs through a handful of ribs right at the mouth of the fitting. Those ribs carry the full pull, while the ribs further along only carry it by being stretched. So the stress is concentrated at the joint, and that is where the system gives way.

Three practical consequences follow:

  1. The fitting is half the rating. A tensile class belongs to a conduit with a specific fitting. Pair the conduit with an unmatched or loose connector and the system can let go well below its class. Use the fitting series made for that conduit, such as the PSC-PG and PSC-M straight connectors for PA-6 conduit.
  2. Size matters. A fitting one size too large grips fewer rib flanks. If the conduit can be wiggled in the fitting by hand, it will not reach its tensile class.
  3. Seat it fully. A conduit pushed only partly into a fitting engages fewer ribs. Most fittings give an audible click when the conduit is home. Check it.

Tensile is not the same as hanging load

Datasheets for conduit list several mechanical ratings side by side, and they are easy to mix up. For PA-6 Heavy Weight FR:

RatingValueWhat it describes
Tensile strength500 N (Class 3)A short pull along the axis of the conduit and fitting assembly
Suspended load150 N (Class 3)A weight hung from the conduit for a sustained period
Compression750 N (Class 3)A crushing force across the diameter
Impact at +23 °C> 20 J (Class 5)A falling weight striking the conduit

The figure designers most often get wrong is the hanging load. A sustained load is much harsher than a brief pull, because plastics creep: under a constant force, they slowly stretch over hours and days. That is why the suspended-load rating, 150 N, is less than a third of the tensile figure. If a vertical drop of conduit and cable weighs more than about 15 kg, it needs its own support, not just the top fitting.

Where 500 N shows up in real installations

  • Cable pulling. Pulling a heavy bundle through a long run with several bends puts tension on the whole conduit system. If cable sticks, a fitter can easily exceed 500 N by hand. Pull from a draw wire, use lubricant on long runs, and never use the conduit itself as the pull rope.
  • Moving machinery. On doors, slides and swinging panels, a conduit that is a few centimetres too short becomes a tension member at the end of travel. Leave a slack loop and check full travel before fixing.
  • Floor runs and walkways. A conduit caught by a boot or a trolley wheel sees a sudden pull at its nearest fitting. Route away from walkways, or use cable covers.
  • Vertical drops. As above: support the weight with clamps along the run, and let the fittings seal and terminate rather than carry load. Our vibration checklist covers clamp spacing on moving machinery.
Packed coil of Synflex corrugated conduit with a loose length looped over it
Figure 2. Synflex corrugated conduit, coiled and wrapped for dispatch from Faridabad.

A note on PA-6 and moisture

Polyamide 6 absorbs a little water from the air. Straight off the extrusion line, it is at its driest, stiffest and least tough. After some days in normal humidity it becomes slightly softer and considerably tougher. Test standards condition samples before testing for this reason, and it is also why a fresh coil can feel stiffer than the same conduit a few weeks later. None of this changes the class, but it is worth knowing if you compare results between labs or between coils.

What this means for your specification

  • Specify tensile strength as a system property: conduit plus fitting series, at the size you will use.
  • For general machine wiring and building services, Class 3 (500 N) is a sensible minimum for flexible conduit.
  • Do not use the tensile figure for hanging weights. Use the suspended-load rating and support the run.
  • Ask your supplier whether the figure is a class rating, a test-to-failure result, or both. Ours is both: the product is rated Class 3, and the test above shows where it actually lets go.

Tension is one load case; repeated bending is another. See how the same conduit handled 5,000 flexing cycles at −40 °C and +150 °C.